Gas detectors
Explosion-proof H₂ monitoring for battery energy storage systems, supporting hazardous-area detection and integration with safety control systems.
Technical Specifications
Item
Specification
Dimensions
Detector: 113 × 78 × 50 mm; Monitor: 163 × 82 × 34.5 mm
Weight
Detector: 410 g; Monitor: 460 g
Protection Rating
Detector: IP65; Monitor: IP20
Service Life
10 years
Target Gas
H₂
Detection Principle
Thermal Conductivity
Measurement Range
0–100% LEL
Measurement Accuracy
±3% LEL (0–50% LEL); ±5% LEL (50–100% LEL)
Alarm Response Time
<15 s
Sensor Response Time (T90)
<30 s
Operating Voltage
24 V DC (18–32 V DC)
Operating Current
Detector: ≤10 mA; Monitor: ≤50 mA
Maximum Current
Detector: ≤15 mA; Monitor: ≤60 mA
Operating Temperature / Humidity
−40 to +75°C; 5–95% RH
Atmospheric Pressure / Altitude
70–110 kPa; up to 3,000 m
Interfaces
Detector: CAN; Monitor: CAN / RS-485
Standalone Configuration
RS-485; optional 4–20 mA
Monitoring Capacity
Up to 120 detectors
Approvals / Compliance
CE; ATEX; RoHS; EMC; REACH